EMERGENCY PORTABLE RECTIFIER 


 

 

The feature of Emergency Portable Rectifier

Specification

Electrical Specifications

INPUT Voltage Three-phase 380Va.c. One phase 200Va.c.
Voltage range -20% ~+ 15%
Frequency 45 ~ 65Hz
OUTPUT  Voltage (2 programmable ranges) 1.9  ~ 14.5Vdc

14.5  ~ 73.1Vdc

Static regulation < 1%
Dynamic regulation <  8%    
Psophometric noise < 2 mV
Ripple < 100 mV peak to peak
Current (variation step = 1A) 5 ~ 100A
Protection Over-voltage, current

Environmental Specifications

Temperature Working  -10°~ + 40°C
Storage  -25°~ + 70°C
Relative humidity £ 95% at 40°C 
Acoustic noise < 45 dBA at 1 meter
MTBF 140,000 hr at 30°C
Weight 24Kg
Dimensions  535x220x435mm (WxDxH)
Altitude £ 1000m

 